AC solid state relay off leakage small load - PLC Playground troubleshooting guide

AC Solid-State Relay Is Off but the Load Glows? Check Leakage

An off-state solid-state relay can pass a small current. A sensitive load may glow or fail to release even though the control input is off. Compare leakage specifications with the load behavior before declaring the relay shorted.

AC SSR example; leakage and failure behavior are product-specific.

What is happening?

Semiconductor output circuits and internal snubbers can contribute off-state leakage. The amount and acceptable load types depend on the model. Off-state indication is not electrical isolation.

Check these five things

  1. Confirm the SSR output type and exact part number.

  2. Read leakage and minimum-load specifications.

  3. Compare the load holding or response characteristics.

  4. Have qualified personnel use an approved diagnostic method.

  5. Select a manufacturer-supported load-interface solution if needed.

Worked example

A teaching indicator draws so little current that SSR leakage produces a faint light while the control input is off. A larger lamp behaves differently. The observation can be compatible with the specification, but a failed-short SSR must still be distinguished through the approved test.

Quick diagnostic reference

Evidence Question
Small residual effect Specified leakage sufficient?
Full load operation Possible failed output?
Control input off Does not establish isolation

The mistake to avoid

Do not add an arbitrary resistor or treat the output as safe to touch. Any load adaptation needs voltage, power, protection, and installation review.

How to verify the fix

Confirm both commanded operation and off-state behavior with the intended load. Document the approved interface and isolation method separately.